簡介
TCW/CCW
The device allows to supply with hot and cold water the hydraulic test benches for laboratory, production and endurance applications.
我要諮詢The device allows to supply with hot and cold water the hydraulic test benches for laboratory, production and endurance applications.
The TCW/CCW generators are made up of two independent plants used to produce and store hot and cold water and recovery the return mixed water. The refrigeration circuit uses a silenced airtight SCROLL type compressor that allows a high power efficiency, lower electric consumption and lower noise. SCROOL compressor reduces the risk of valves failure, high frequency failure in other compressor type. The cooling plant consist in a forced air condenser with fans controlled by inverter, an external tank heat exchanger, an air-mixing pump and an expansion device with thermostatic valve with by-pass on hot gas. The heating plant consists of three heating elements and one water circulator. The TCW/CCW group works with closed circuit. The water used on the bench is recovered and sent again to the generator where it is heated/cooled again at the temperatures required for the test.
TCW B2 (axial fans) | CCW B2 (centrifugal fans) | |
Cooling power | 23 kW | 23 kW |
Heating power | 24 kW | 24 kW |
Maximum operating range | hot water 40 ÷ 90 °C cold water 5 ÷ 25 °C |
hot water 40 ÷ 90 °C cold water 5 ÷ 25 °C |
Recommended operating range | hot water 40 ÷ 90 °C cold water 10 ÷ 25 °C |
hot water 40 ÷ 90 °C cold water 10 ÷ 25 °C |
Typical stability in dynamic condition at 50% of flow-rate | ±0,5 °C | ±0,5 °C |
Limit ambient temperature | -10 ÷ 45 °C | -10 ÷ 45 °C |
Internal tanks | 300+300 L | 300+300 L |
Continuous flow-rate with supply at 15 and 65 °C and 40 °C mixed water temperature. |
12+12 L/min | 12+12 L/min |
Noise level | 75 dB | 75 dB |
Fans flow-rate | 10.000 m³/h | 11.000 m³/h |
Size | 2.300 x 1.200 x (h) 2.050 mm | 2.300 x 1.200 x (h) 2.300 mm |
Weight | 680 kg | 720 kg |
Electric supply | 400 V – 3 Ph – 50 Hz | 400 V – 3 Ph – 50 Hz |
Internal secondary | 24 V AC | 24 V AC |
Total power | 36,0 kW | 37,6 kW |
Max absorbed current | 58,2 A | 61,0 A |
TCW E0 (axial fans) | CCW E0 (centrifugal fans) | |
Cooling power | 46 kW | 46 kW |
Heating power | 48 kW | 48 kW |
Maximum operating range | hot water 40 ÷ 90 °C cold water 5 ÷ 25 °C |
hot water 40 ÷ 90 °C cold water 5 ÷ 25 °C |
Recommended operating range | hot water 40 ÷ 90 °C cold water 10 ÷ 25 °C |
hot water 40 ÷ 90 °C cold water 10 ÷ 25 °C |
Typical stability in dynamic condition at 50% of flow-rate | ±0,5 °C | ±0,5 °C |
Limit ambient temperature | -10 ÷ 45 °C | -10 ÷ 45 °C |
Internal tanks | 400+400+100 L | 400+400+100 L |
Continuous flow-rate with supply at 15 and 65 °C and 40 °C mixed water temp. | 24+24 L/min | 24+24 L/min |
Noise level | 75 dB | 75 dB |
Fans flow-rate | 15.000 m³/h | 16.500 m³/h |
Size (with wheels) | 2.700 x 1.600 x (h) 2.050 mm | 2.700 x 1.600 x (h) 2.300 mm |
Weight | 1.800 kg | 1.900 kg |
Electric supply | 400 V – 3 Ph – 50 Hz | 400 V – 3 Ph – 50 Hz |
Internal secondary | 24 V AC / 24 V DC | 24 V AC / 24 V DC |
Total power | 70,2 kW | 73,0 kW |
Max absorbed current | 120 A | 130 A |