The NEW MI 2892 Power Master is a hand-held three phase power quality analyser with a large easy-to-read graphical colour display enabling the user to detect harmonics, phasors and waveforms anomalies in the installation simply by connecting the device. The instrument is designed for a long term recording as well as for troubleshooting power quality problems in three-phase and single-phase power distribution systems. The handy Quick Set buttons makes the instrument more user friendly and are allowing faster data overview for troubleshooting. Advanced PC SW package PowerView3 enables detailed analysis of recorded data, direct reading from the microSD memory card, analysis of long term records and automatic creation of professional test report.
MEASURING FUNCTIONS:
Voltage: TRMS, peak, crest factor (4-channel);
Current: TRMS, peak, crest factor (4-channel);
Power (active, reactive, apparent);
Power measurements fully compliant with IEEE 1459 (active, nonactive, fundamental, harmonic, load unbalance);
Unbalance, flicker measurement;
Harmonic and interharmonic analysis up to 50th harmonics, THD measurement;
Energy (active, reactive, generated, consumed);
Capturing and recording of power supply events (shutdowns, interruptions, swells, dips);
Inrush currents monitoring and recording;
Waveform/inrush displaying, snapshot and recording;
Transients recording;
Power quality analysis according to EN 50160;
Recording up to 7 adjustable alarms;
Temperature measurement;
Power factor cos ϕ.
MAIN FEATURES:
4 voltage channels with wide measurement range: 0 ... 1000 Vrms (CAT III / 1000 V);
4 current channels with support for automatic clamp recognition and “on instrument“ range selection;
Automatic Smart Clamp detection and Smart Clamp range selection;
Compliance with power quality standard IEC 61000-4-30 Class A;
Complete power quality analysis according to EN 50160 including signalling and interharmonics;
Support for microSD memory card (8-GB supplied with the instrument) up to 32GB;
Color-coded input terminals and terminal labels to suit your application region;
Intuitive main menu and large icons that makes the equipment very easy to navigate and configure;
Powerful PC SW PowerView3 enables downloading, view, analysis of recorded data and professional report creation;
Flexible clamps (without additional power supply) are included in the standard set.
APPLICATION:
Energy consumption optimization;
Power quality assessment and troubleshooting in low and middle voltage electrical systems;
Checking power correction equipment performance;
Long-term analysis;
Predictive maintenance;
Verification of electrical system capacity before adding loads.
Voltage inputs / AC+DC:
Number of inputs: 5
Nominal voltage range (L – N): Phase (L-N): 50 ÷ 1000 VRMS; Line (L-L): 50 ÷ 1730 VRMS
Measuring range: 10% ÷ 150% of nominal voltage
Accuracy: IEC 61000-4-30 Class A, ±0.1% of nominal voltage,
Sampling rate: 7 kSamples per sec @ 50/60 Hz, sync with mains freq.
Mains frequency range: 42,5 ÷ 69,0 Hz ±10 mHz
Current inputs / AC+DC:
Number of inputs: 4
Measuring range (with A1227 flex clamps): 3 ÷ 6000 ARMS ±1.5% of m.v.
Measuring range (with A1281 iron clamps): 50 m ÷ 1200 ARMS ±0.5% of m.v.
STANDARDS:
Functionality: EN 61010-1
Measurements:
IEC/EN 61000-4-30,Class A;
IEC/EN 61557-12;
IEC/EN 61000-4-7, Class I;
IEC/EN 61000-4-15;
EN 50160;
IEEE 1448;
IEEE 1459;
IEEE 519
Electromagnetic compatibility (EMC): EN 61326
Please feel free to contact for detailed specifications, accessories, software and options.