Detailed analysis of test results using DV-Win software
Interchangeable test leads with Three-phase Winding Ohmmeters & Tap Changer Analyzers TWA
Built-in Printer: Built-in thermal printer, 112 mm (4.4 in) wide, is an optional accessory.
Memory: Store 200 test records. Each record consists of 50 test readings.
Application:
Turns ratio measurement
Turns ratio deviation calculation
Excitation current measurement
Phase angle measurement
Automatic vector group detection
Verification of demagnetization process
Magnetic balance test
System Overview:
TRT03 is a three-phase, fully automatic test set specially designed for turns ratio, phase shift, and excitation current measurements of power, distribution and instrument transformers.
The test set can be used to test single-phase and three-phase transformers, both with and without taps in accordance with the requirements of the IEC 60076-1 standard.
DV-Win Software:
The DV-Win software is included in the purchase price, and all its updates are free of charge.
The software allows full control of TRT03 functions from a PC, and downloading test results from the instrument’s internal memory.
All results are presented both numerically and graphically, for an easy and convenient analysis.
Test results can be directly exported to excel document.
Customized test report can be generated, edited, saved in several file formats including pdf, and printed.
Mains Power Supply:
Connection: according to IEC/EN60320-1; UL498, CSA 22.2
Mains supply: 90 – 264 V AC, 50/60 Hz or 110 – 350 V DC
Input power: 200 VA
Fuse: 2 A / 250 V, type F, not user replaceable
Output Data (models/Test Voltages):
TRT03A: 8, 40, 100 V AC
TRT03B: 10, 40, 100 V AC
TRT03C: 8, 40, 80 V AC
Measurement:
Turns ratio measuring range: 0,8 – 50 000
Turns ratio resolution: 5 digits
Typical turns ratio accuracy:
@80 or 100 V AC
0,8 – 999: ±0,05%
1 000 – 3 999: ±0,05%
4 000 – 14 999: ±0,1%
15 000 – 19 999: ±0,2%
20 000 – 50 000:±0,25%
@40 V AC
0,8 – 999: ±0,05%
1 000 – 3 999: ±0,1%
4 000 – 14 999: ±0,2%
15 000 – 20 000: ±0,3%
@8 or 10 V AC
0,8 – 999: ±0,05%
1 000 – 3 999: ±0,1%
4 000 – 15 000: ±0,2%
Excitation current range: 0 – 2 A
Excitation current resolution:
0,0000 – 9,9999 mA: 0,1 μA
10,000 – 99,999 mA: 1 μA
100,00 – 999,99 mA: 10 μA
1,0000 – 2,0000 A: 100 μA
Typical excitation current accuracy: ±(0,25% rdg + 500 μA)
Phase angle range: 0 – 360º
Phase angle resolution: 0,01º
Typical phase angle accuracy: ±0,05º
Display:
LCD screen 20 characters by 4 lines;
LCD display with backlight, visible in bright sunlight
Interface:
USB (standard)
RS232 (optional)
Data Storage: Store up to 10 000 test results
Please feel free to contact for detailed specifications, accessories, software and options.