The MI 2885 Master Q4 is an ideal troubleshooting tool. The recorders are designed to automatically record all important data and waveforms of voltage events like Dips and Swells.
In addition the user can set 7 optional triggers for capturing waveforms of selected quantities.
A large easy-to-read graphical colour display enabling the user to detect harmonics, phasors and waveforms anomalies in the installation simply by connecting the device.
The handy Quick Set buttons makes the instrument more user friendly and are allowing faster data overview. The instrument is designed for a long term recording as well as for troubleshooting power quality problems in threephase and single-phase power distribution systems.
Advanced PC SW package PowerView3 enables detailed analysis of recorded data, direct reading from the microSD memory card, analysis of long term records and automatic creation of professional test report.
Measuring Functions:
Voltage: TRMS, peak, crest factor (4-channel);
Current: TRMS, peak, crest factor (4-channel);
Power (active, reactive, apparent);
Power measurements fully compliant with IEEE 1459 (active, non active, fundamental, harmonic, load unbalance);
VFD (variable frequency drives);
Unbalance, flicker measurement;
Harmonic and interharmonic analysis up to 50th harmonics, THD measurement;
Energy (active, reactive, generated, consumed);
Capturing and recording of power supply events (shutdowns, interruptions, swells, dips);
Inrush currents monitoring and recording;
Waveform/inrush displaying, snapshot and recording;
Power quality analysis according to EN 50160;
Recording up to 7 adjustable alarms;
Temperature measurement;
Power factor cos φ.
Application:
Power quality assessment and troubleshooting in low and middle voltage electrical systems;
Checking power correction equipment performance;
Long-term analysis;
Predictive maintenance;
Verification of electrical system capacity before adding loads.
Standards:
Functionality: EN 61010-1
Measurements:
IEC/EN 61000-4-30,Class S;
IEC/EN 61557-12;
IEC/EN 61000-4-7, Class I;
IEC/EN 61000-4-15;
EN 50160;
IEEE 1448;
IEEE 1459
Electromagnetic compatibility (EMC): EN 61326
Voltage inputs/AC+DC:
Number of inputs: 5
Nominal voltage range (L – N):
Phase (L-N): 50 ÷ 1000 VRMS
Line (L-L): 50 ÷ 1730 VRMS
Measuring range: 10% ÷ 150% of nominal voltage
Accuracy: IEC 61000-4-30 Class S, ±0.5% of nominal voltage,
Sampling rate: 7 kSamples per sec @ 50/60 Hz, sync with mains freq.
Mains frequency range: 42,5 ÷ 69,0 Hz ±10 mHz
Current inputs/AC+DC:
Number of inputs: 4
Measuring range (with A1227 flex clamps): 3 ÷ 6000 ARMS ±1.5% of m.v.
Measuring range (with A1281 iron clamps): 50 m ÷ 1200 ARMS ±0.5% of m.v.
Please feel free to contact for detailed specifications, accessories, software and options.